Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

65

Installation and Wiring

Chapter 1

Figure 41 - Frame D Relay and Thermistor/Thermal Switch Terminal Block Locations

Control Circuit Input Power

The control circuit must be powered by a clean, external 230V AC or 115V AC
single phase power supply. For frame B and C drives only, a jumper is required
between terminals SA and SB for 115V AC control input power. For frame B
drive SA-SB terminal block location, see

Figure 47

on page

68

. For frame C drive

SA-SB terminal block location, see

Figure 47

on page

68

.

Note:

If the SA-SB terminal block is not configured for the correct input voltage,

“No Fault” (F0) displays on the HIM, if installed.

Table 20 - Control Circuit Wire Sizes and Terminal Specifications

Terminals

Description

U2, V2

Single phase AC power for the control circuits

PE

Safety ground (on frame C drive terminal blocks only)

Terminals

Wire Size and Type

(1)

(1) See Cable and Wiring Recommendations on page

43

for more information.

Tightening Torque
N
m (lbin)

Flexible
(mm

2

)

Multi-core
(mm

2

)

AWG

U2, V2

0.14…1.5

0.14…2.5

26…14

0.5 (4.4)

PE

2.5…10

2.5…10

12…8

2.0 (18.0)

Control pan, to the left of the
HIM cradle.

78 79 35 36 75 76