[Speed Zero Level]
Speed below which the actual speed is considered equal to zero. When a Stop
command is issued and actual speed goes below this value, drive output is
disabled. The value applies to both rotation directions for four quadrant
drives.
Notes: Setting the value of this parameter too low could prevent the proper
functioning of field economy. If Par 107 and/or Par 108 are changed from
their default values it can affect the Speed Loop autotune function (Par
1027). Ideally, set these parameters to the default values when autotuning
the Speed Loop. Values substantially different from defaults will result in an
autotuning fault.
Note: See Speed Zero Function on page

322

for more information.

Default:

Min/Max:
Units:

20

1 / 6000
rpm

16-bit
Int

395,
1027

108

[Speed Zero Delay]
Amount of time that must elapse after the actual speed goes below the value
set in Par 107 [Speed Zero Level] before Par 395 [At Zero Speed] changes
state.
Note: See Speed Zero Function on page

322

for more information.

Default:

Min/Max:
Units:

100

0 / 65535
ms

16-bit
Int

395,
1027

123

[Spd Zero I En]
Enables/Disables the output of the integral section of the speed regulator.
Used in the Zero Speed function.
“Enabled” = The output of the integral section of the speed regulator is

set to zero when the speed reference and the speed feedback are equal to
zero. The I component is enabled when a reference value is entered to
restart acceleration.

“Disabled” = The speed regulator keeps its integral gain component

when the drive is at zero speed.

Note: See Speed Zero Function on page

322

for more information.

Default:

Options:

0 =

0 =
1 =

“Disable”

“Disable”
“Enable”

16-bit
Int

124

[Spd Ref Zero En]
This parameter is only active when Par 125 [Spd Zero P En] = 1 “Enabled”.
Used in the Zero Speed function.
“Enabled” = The proportional gain, equal to Par 126 [Spd Zero P Gain] at

zero speed, is equal to Par 87 [Spd Reg Kp] when the speed reference is
higher than the value defined in Par 106 [Ref Zero Level].

“Disabled” = The proportional gain, equal to Par 126 [Spd Zero P Gain] at

zero speed, is equal to the value in Par 87 [Spd Reg Kp] when the speed
reference or the actual speed is higher than the value defined in Par 106
[Ref Zero Level].

Note: See Speed Zero Function on page

322

for more information.

Default:

Options:

0 =

0 =
1 =

“Disable”

“Disable”
“Enable”

16-bit
Int

125

[Spd Zero P En]
“Enabled” = When both the speed reference value and the actual speed
value = 0, the proportional gain value in Par 126 [Spd Zero P Gain] is active
after the delay time defined in Par 108 [Speed Zero Delay]. Used in the Zero
Speed function.
“Disabled” = The speed regulator keeps its proportional gain component
when the drive is at zero speed.
Note: See Speed Zero Function on page

322

for more information.

Default:

Options:

0 =

0 =
1 =

“Disable”

“Disable”
“Enable”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

Actual Speed

Par 107
[Speed Zero Level]

Par 108 [Speed Zero Delay]

Par 395
[At Zero Speed]

Fwd

Rev

Actual Speed = 0