Troubleshooting Crane Setup - Encoderless

The following faults commonly occur during drive commissioning.

F4 “AC Undervoltage”

If the mains supply is still present, reduce the undervoltage level at P481
[UnderVolt Thresh].

F5 “Arm Overvoltage”

Verify the parameter settings as stated in Set Up the Drive on page

297

.

F94 “TrqProve Spd Band” (Speed deviation fault)

This fault is active only when TorqProve is enabled.

The speed loop tuning is not correct. Increase P434 [Spd Reg BW] or P43
[Total Inertia]. If theses values are too high the regulator will become
unstable.

P1008 [Spd Reg Fdbk] should follow P113 [Ramp Out] as closely as
possible.

The drive is going into current limit. The drive is undersized or
acceleration / deceleration is set too fast.

The brake is not opening. Check for faulty brake operation.

For more fault information, refer to Chapter 4 Troubleshooting, starting on page

215

.