Applications file – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 157

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

157

Programming and Parameters

Chapter 3

Applications File

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

PPLIC

AT

IONS

PI Co

n

trol

695

[PI Steady Thrsh]
Feed–forward threshold for PI.
If the value if Par 758 [Feed Fwd PID] is less than the value of Par 695 [PI Steady

Thrsh] the integral regulation will be locked and the proportional gain assumes
the value set in Par 793 [PI Init Prop Gn].

When the value of Par 758 [Feed Fwd PID] exceeds the value of Par 695 [PI

Steady Thrsh], the integral regulation with the gain set in Par 734 [PI Init Intgl
Gn] will be enabled.

The Proportional / Integral (PI) block will maintain the gain values specified in

Pars 793 [PI Init Prop Gn] and 734 [PI Init Intgl Gn] for the time specified in Par
731 [PID Steady Delay]; once this time delay has elapsed, the values of [PI Init
Prop Gn] and [PI Init Intgl Gn] will be brought automatically to the values
specified in Pars 765 [PI Prop Gain PID] and 764 [PI Integral Gain], respectively.

Default:

Min/Max:

0

0 / 10000

16-bit
Int

758

731

[PID Steady Delay]
The amount of time for which the gains in Pars 793 [PI Init Prop Gn] and 734 [PI Init
Intgl Gn] will remain enabled after feed–forward has exceeded the threshold value
defined in Par 695 [PI Steady Thrsh].

Default:

Min/Max:
Units:

0

0 / 60000
ms

16-bit
Int

695,
734,
793

734

[PI Init Intgl Gn]
The initial value of the integral gain. This parameter is active when feed–forward is
greater than the value defined in Par 695 [PI Steady Thrsh], or Par 769 [Enable PI]
transitions from “0” (low) to “1” (high) and the amount of time defined in Par 731
[PID Steady Delay] has elapsed.

Default:

Min/Max:

10.00

0.00 / 100.00

Real

695,
731,
769

764

[PI Integral Gain]
Integral gain of the PI block.

Default:

Min/Max:

10.00

0.00 / 100.00

Real

765

[PI Prop Gain PID]
Proportional gain of the PI block.

Default:

Min/Max:

10.00

0.00 / 100.00

Real

769

[Enable PI]
Enables/Disables the PI portion of the PID regulator. If assigned to a digital input,
this parameter must be brought at a high logical level (+24V).

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

771

[PI Output]
Output value of the PI block, adapted to the value between the values defined in
Pars 784 [PI Upper Limit] and 785 [PI Lower Limit]. When the drive is turned on,
the value of this parameter is acquired automatically based on the value of Par 779
[PI Central v sel] x 1000.

Default:

Min/Max:

Read Only

0 / 10000

16-bit
Int

784,
785,
779

776

[PI Central v1]
The first value that can be selected, via Par 779 [PI Central v sel], as the initial
output of the PID regulator’s integral component (corresponding to initial diameter
1). The value entered in this parameter must be less than the value set in Par 784
[PI Upper Limit] and greater than the value set in Par 785 [PI Lower Limit].

Default:

Min/Max:

0.00

Par 785 [PI Lower Limit] / Par 784 [PI
Upper Limit]

Real

784,
785,
779

777

[PI Central v2]
The second value that can be selected, via Par 779 [PI Central v sel], as the initial
output of the PID regulator’s integral component (corresponding to initial diameter
2). The value entered in this parameter must be less than the value set in Par 784
[PI Upper Limit] and greater than the value set in Par 785 [PI Lower Limit].

Default:

Min/Max:

0.00

Par 785 [PI Lower Limit] / Par 784 [PI
Upper Limit]

Real

784,
785,
779

778

[PI Central v3]
The third value that can be selected, via Par 779 [PI Central v sel], as the initial
output of the PID regulator’s integral component (corresponding to initial diameter
3). The value entered in this parameter must be less than the value set in Par 784
[PI Upper Limit] and greater than the value set in Par 785 [PI Lower Limit].
Note: This parameter can be assigned to an analog input.

Default:

Min/Max:

0.00

Par 785 [PI Lower Limit] / Par 784 [PI
Upper Limit]

Real

784,
785,
779

A

A

A

A

A

A

A

A

A

A

Advertising
This manual is related to the following products: