Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

277

Application Notes

Appendix C

Analog Input Signal Comparison

This feature provides an indication via the HIM or a digital output when the
signal of analog input 1 has reached a limit above or below a set reference point.

Calculations used to determine Pars1042 [Anlg In1 Cmp] and 1043 [Anlg In1
Cmp Err]:

[Anlg In1 Cmp] = (comparison value) x 10000 / (max. reference value)

[Anlg In1 Cmp Err] = (tolerance value) x 10000 / (max. reference value)

Example 1:

An application requires an indication via a digital output that the motor speed is
within 100 rpms of 700 rpm.

Par 45 [Max Ref Speed] = 1500 rpm (maximum reference value)

For Analog Input 1, 10V or 20mA sets the maximum value of Par 44
[Speed Ref A] = Par 45 [Max Ref Speed]

Configure the following:

Set Par 70 [Anlg In1 Sel] = “Speed Ref A”

Set [Digital Outx Sel] = “Input1 Cmp” (Par 1045 [Anlg In1 Cmp Eq])

Set Par 1042 [Anlg In1 Cmp] = 4667 (700 x 10000 / 1500)

Set Par 1043 [Anlg In1 Cmp Err] = 666 (100 x 10000 / 1500 )

Anlg In1 Cmp

0

0 ms

Anlg In1 Cmp Eq

Anlg In1 Cmp Dly

Anlg In1 Cmp Err

0