Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

181

Programming and Parameters

Chapter 3

UTILIT

Y

Fa

u

lt

s

1361
1362
1363
1364
1365
1366
1367
1368
1369
1370

[Fault 1 Time]
[Fault 2 Time]
[Fault 3 Time]
[Fault 4 Time]
[Fault 5 Time]
[Fault 6 Time]
[Fault 7 Time]
[Fault 8 Time]
[Fault 9 Time]
[Fault 10 Time]
The time between initial drive power up and the occurrence of the associated trip
fault.

Default:

Min/Max:
Units:

Read Only

0.000 / 134000000.000
hr.

Real

1371 [Fault Arm Amps]

Captures and displays the armature current (as a percentage of rated current) at
the time of the last fault.

Default:

Min/Max:
Units:

Read Only

–/+200
%

16-bit
Int

1372 [Fault Speed]

Captures and displays the output speed (rpm) of the drive at the time of the last
fault.

Default:

Min/Max:
Units:

Read Only

– / +8192
rpm

16-bit
Int

1373 [Fault Field Amps]

Captures and displays the field current (as a percentage of rated current) at the
time of the last fault.

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

1374 [Fault Voltage]

Captures and displays the armature voltage at the time of the last fault.

Default:

Min/Max:
Units:

Read Only

- / + 999.00
Vdc

Real

Al

arms

203

[OverVolt Flt Cfg]
Determines the response of the drive to an overvoltage condition (F5 “Arm
Overvoltage”).
Note: See Chapter 4 for a list of alarm and fault descriptions.

Default:

Options:

2 =

0 =
1 =
2 =

“Fault”

“Ignore”
“Alarm”
“Fault”

16-bit
Int

354

[Aux Inp Flt Cfg]
Determines the response of the drive to an external fault condition (F2 “Auxiliary
Input”), i.e., no voltage at the digital input terminal assigned to [Digital Inx Sel]
with a value of 14 “Aux Fault”.
Notes: See Chapter 4 for a list of alarm and fault descriptions. Option 3 was
changed from “Quick Stop” to “Fast Stop” for firmware version 2.001.

Default:

Options:

2 =

1 =
2 =
3 =
4 =
5 =

“Fault”

“Alarm”
“Fault”
“Fast Stop”
“Normal Stop”
“CurrLim Stop”

16-bit
Int

365

[OverTemp Flt Cfg]
Determines the response of the drive to a motor over temperature condition (F16
“Motor Over Temp”).
Notes: See Chapter 4 for a list of alarm and fault descriptions. Option 3 was
changed from “Quick Stop” for firmware version 2.001.

Default:

Options:

2 =

0 =
1 =
2 =
3 =
4 =
5 =

“Fault”

“Ignore”
“Alarm”
“Fault”
“Fast Stop”
“Normal Stop”
“CurrLim Stop”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

ATTENTION: Setting this parameter to 0 “Ignore” or 1 “Alarm”, could result in motor and/or equipment damage. If set to
“Ignore” or “Alarm”, it is strongly recommended that an external means of protecting against this condition be provided.

A

ATTENTION: Setting this parameter to 1 “Alarm”, could result in motor and/or equipment damage. If set to “Alarm”, it is
strongly recommended that an external means of protecting against this condition be provided.

A

ATTENTION: Setting this parameter to 0 “Ignore” or 1 “Alarm”, could result in motor and/or equipment damage. If set to
“Ignore” or “Alarm”, it is strongly recommended that an external means of protecting against this condition be provided.

Advertising