Appendix C

Application Notes

SLAT Min Mode

In SLAT Min mode, a speed reference that forces the speed regulator into
saturation (the speed reference is slightly above the speed feedback) is typically
configured. In this case the drive follows the torque reference until there is a
breakage or slippage in the application.

When the drive is following a torque reference (torque mode) in SLAT Min
mode, either one of two conditions will force the drive into following the speed
reference (speed mode):

1.

The output of the speed regulator becomes less than the torque reference.

2.

The speed error becomes negative (the speed feedback becomes greater
than the speed reference). This is forced speed mode.

Parameter 15 [SLAT Err Stpt] and parameter 16 [SLAT Dwell Time] let you set
some hysteresis for turning off the forced speed mode. They are set to “0” as
default so that there is no hysteresis. In SLAT Min mode, Par 15 [SLAT Err Stpt]
sets how much less the speed feedback is than the speed reference before turning
off the forced speed mode. Par 16 [SLAT Dwell Time] sets how long the speed
error must exceed the SLAT error set point before turning off the forced speed
mode.

At the time the drive switches from torque mode to forced speed mode, the speed
regulator integral part is pre-loaded with the InternalTorque Reference (ITR) or
Par 14 [Selected TorqRef ] to create a smooth transition.

In order for the drive to switch from speed mode to torque mode, forced speed
mode (if active) must first be turned off. Forced speed mode will turn off when
the speed error is greater than the SLAT error setpoint for the SLAT dwell time.
With default parameter settings, this will occur when the speed error becomes
positive.

When Forced Speed Mode is off, the drive will switch back to torque mode when
the speed regulator output becomes greater than the torque reference.

Application

Dependant Speed

Reference Bias

Motor Speed

Feedback

+

-

Speed Error

PI

Regulator

Speed Regulator

Output (SRO)

Min

Select

External Torque
Reference (ETR)

Internal Torque
Reference (ITR)

Off

Forced Speed

Mode (FSM )

FSM =

On

Low Pass

Filter

On

Off

Speed Error < 0

Speed Error > SLAT Setpoint

for SLAT Dwell Time

FSM State Controller

Par 15 [SLAT Err Stpt]

Par 16 [SLAT Dwell Time]