9.3
Display Group Parameters
Displays the output frequency present at terminals T1, T2, and T3
(U, V, and W).
Displays the value of the active frequency command. The
commanded frequency is displayed even if the drive is not running.
Important:
The frequency command can come from a number of
sources. Refer to section 6.6, Start and Speed
Reference Control, for more information.
Displays the output current present at terminals T1, T2, and T3 (U,
V, and W).
Displays the output voltage present at terminals T1, T2, and T3 (U,
V, and W).
d001 Output Freq
Range:
0.0 to Maximum Freq (P035)
Default:
Read Only
See also:
d002, d010, P034, P035, P038
d002 Commanded Freq
Range:
0.0 to Maximum Freq (P035)
Default:
Read Only
See also:
d001, d013, P034, P035, P038
d003 Output Current
Range:
0.00 to (Drive Rated Amps x 2)
Default:
Read Only
See also:
N/A
d004 Output Voltage
Range:
0 to Drive Rated Volts
Default:
Read Only
See also:
P031, A084, A088