Installing Control Wiring

6-5

Table 6.3 – Control Terminal Definitions and Related Parameters

No.

Signal

Default

Description

Parameter

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

–

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Analog Output Select DIP
Switch

0-10 V

Sets analog output to either voltage or current. Setting must match Analog
Out Sel (A065).

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01

Stop

1, 4

Coast

The factory-installed jumper or a normally closed input
must be present for the drive to start.

P036

1, 4

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To
disable reverse operation, see Reverse Disable (A095).

P036, P037

03

Dir/Run REV

Not Active

P036, P037, A095

04

Digital Common

–

For digital inputs. Electronically isolated with digital
inputs from analog I/O and opto outputs.

05

Digital Input 1

Preset Freq

Program with Digital In1 Sel (A051).

A051

06

Digital Input 2

Preset Freq

Program with Digital In2 Sel (A052).

A052

07

Digital Input 3

Local

Program with Digital In3 Sel (A053).

A053

08

Digital Input 4

Jog Forward

Program with Digital In4 Sel (A054).

A054

09

Opto Common

-

For opto-coupled outputs. Electronically isolated with
opto outputs from analog I/O and digital inputs.

11

+24V DC

–

Referenced to Digital Common.Drive supplied power for
digital inputs. Maximum output current is 100 mA.

12

+10V DC

–

Referenced to Analog Common. Drive supplied power
for digital 0-10 V external potentiometer. Maximum
output current is 15 mA.

P038

13

+/-10V In

5

Not Active

For external 0-10 V (unipolar) or +/-10 V (bipolar) input
supply (input impedance = 100 k Ohm) or potentiometer
wiper.

P038, A051-A054,
A123, A132

14

Analog Common

–

For 0-10 V In or 4-20 mA In. Electronically isolated with
analog inputs and outputs from digital I/O and opto
outputs.

15

4-20mA In

5

Not Active

For external 4-20 mA input supply
(input impedance = 250 Ohm).

P038, A051-A054,
A132

16

Analog Output

OutFreq 1-10

The default analog output is 0-10 V. To convert to a
current value, change the Analog Output Select DIP
Switch to 0-20 mA. Program with Analog Out Sel (A065).
Max analog value can be scaled with Analog Out High
(A066).
Maximum Load: 4-20 mA = 525 ohm (10.5 V)
0-10 V = 1k ohm (10 mA)

A065, A066

17

Opto Output 1

MotorRunning

Program with A058 (Opto Out1 Sel)

A058, A059, A064

18

Opto Output 2

At Frequency

Program with A061 (Opto Out2 Sel)

A061, A062, A064

19

RS485 Shield

-

Terminal should be connected to safety ground- PE
when using the RS485 communications port.

1

Important: I/O Terminal 01 is always a coast-to-

stop input except when Start Source (P036) is set
to “3-Wire Control.” In three-wire control, I/O
Terminal 01 is controlled by Stop Mode (P037). All
other stop sources are controlled by Stop Mode
(P037).

P036 (Start Source)

Stop

I/O Terminal 01 Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

4

2-Wire

Per P037

Coast

RS485 Port

Per P037

Coast

Important: The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this

jumper when using I/O Terminal 01 as a stop or enable input.

2

Two-wire control shown. For three-wire control, use a momentary input

on I/O Terminal 02 to

command a start. Use a maintained input

for I/O Terminal 03 to change direction.

3

When using an opto output with an inductive load such as a relay, install recovery diode parallel to the

relay as shown to prevent damage to the output.

4

When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing

a coast to stop without software interpretation.

5

0-10 V In and 4-20 mA In are distinct input channels and may be connected simultaneously. Inputs may

be used independently for speed control or jointly when operating in PID mode.