Installing Control Wiring

6-5

Table 6.3 – Control Terminal Definitions and Related Parameters

No.

Signal

Default

Description

Parameter

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Analog Output Select DIP
Switch

0-10 V

Sets analog output to either voltage or current. Setting must match Analog
Out Sel (A065).

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01

Stop

1, 4

Coast

The factory-installed jumper or a normally closed input
must be present for the drive to start.

P036

1, 4

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To
disable reverse operation, see Reverse Disable (A095).

P036, P037

03

Dir/Run REV

Not Active

P036, P037, A095

04

Digital Common

For digital inputs. Electronically isolated with digital
inputs from analog I/O and opto outputs.

05

Digital Input 1

Preset Freq

Program with Digital In1 Sel (A051).

A051

06

Digital Input 2

Preset Freq

Program with Digital In2 Sel (A052).

A052

07

Digital Input 3

Local

Program with Digital In3 Sel (A053).

A053

08

Digital Input 4

Jog Forward

Program with Digital In4 Sel (A054).

A054

09

Opto Common

-

For opto-coupled outputs. Electronically isolated with
opto outputs from analog I/O and digital inputs.

11

+24V DC

Referenced to Digital Common.Drive supplied power for
digital inputs. Maximum output current is 100 mA.

12

+10V DC

Referenced to Analog Common. Drive supplied power
for digital 0-10 V external potentiometer. Maximum
output current is 15 mA.

P038

13

+/-10V In

5

Not Active

For external 0-10 V (unipolar) or +/-10 V (bipolar) input
supply (input impedance = 100 k Ohm) or potentiometer
wiper.

P038, A051-A054,
A123, A132

14

Analog Common

For 0-10 V In or 4-20 mA In. Electronically isolated with
analog inputs and outputs from digital I/O and opto
outputs.

15

4-20mA In

5

Not Active

For external 4-20 mA input supply
(input impedance = 250 Ohm).

P038, A051-A054,
A132

16

Analog Output

OutFreq 1-10

The default analog output is 0-10 V. To convert to a
current value, change the Analog Output Select DIP
Switch to 0-20 mA. Program with Analog Out Sel (A065).
Max analog value can be scaled with Analog Out High
(A066).
Maximum Load: 4-20 mA = 525 ohm (10.5 V)
0-10 V = 1k ohm (10 mA)

A065, A066

17

Opto Output 1

MotorRunning

Program with A058 (Opto Out1 Sel)

A058, A059, A064

18

Opto Output 2

At Frequency

Program with A061 (Opto Out2 Sel)

A061, A062, A064

19

RS485 Shield

-

Terminal should be connected to safety ground- PE
when using the RS485 communications port.

1

Important: I/O Terminal 01 is always a coast-to-

stop input except when Start Source (P036) is set
to “3-Wire Control.” In three-wire control, I/O
Terminal 01 is controlled by Stop Mode (P037). All
other stop sources are controlled by Stop Mode
(P037).

P036 (Start Source)

Stop

I/O Terminal 01 Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

4

2-Wire

Per P037

Coast

RS485 Port

Per P037

Coast

Important: The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this

jumper when using I/O Terminal 01 as a stop or enable input.

2

Two-wire control shown. For three-wire control, use a momentary input

on I/O Terminal 02 to

command a start. Use a maintained input

for I/O Terminal 03 to change direction.

3

When using an opto output with an inductive load such as a relay, install recovery diode parallel to the

relay as shown to prevent damage to the output.

4

When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing

a coast to stop without software interpretation.

5

0-10 V In and 4-20 mA In are distinct input channels and may be connected simultaneously. Inputs may

be used independently for speed control or jointly when operating in PID mode.