Parameter Descriptions

9-13

Sets the trip point for the output relay if the value of Relay Out Sel
(A055) is 6, 7, 8, 10, 16, 17, 18, or 20. See table 9.1.

A056 Relay Out Level

Range:

0.0 to 9999 (see table 9.1)

Default:

0.0

See also:

A055, A058, A061

32

Table 9.1 – Trip Points for Digital Output Relay

A055 Setting

A056 Range

6 (Above Freq)

0 to 400 Hz

7 (Above Cur)

0 to 180%

8 (Above DCVolt)

0 to 815 V

10 (Above Anlg V)

0 to 100%

16 (Timer Out)

0.1 to 9999 seconds

17 (Counter Out)

1 to 9999 counts

18 (Power Factor Angle)

1 to 180 degrees

20 (ParamControl)

0, 1