Rockwell Automation MD65 User Manual Version 2.0 User Manual
Page 70

9-16
MD65 AC Drive User Manual
21 = NonRec Fault: Value set in Auto Rstrt Tries (A092) is
exceeded, Auto Rstrt Tries (A092) is not enabled, or a
non-resettable fault has occurred.
22 = EM Brk Cntrl: EM brake is energized. Program EM Brk Off
Delay (A160) and EM Brk On Delay (A161) for desired action.
Determines the on/off point for the opto outputs when Opto Outx Sel
(A058 or A061) is set to option 6, 7, 8, 10, 16, 17, 18, or 20. Refer to
table 9.2.
Determines the logic (Normally Open/NO or Normally Closed/NC)
of the opto outputs. Refer to table 9.3.
A059
A062
Opto Out1 Level
Opto Out2 Level
Range:
0.0 to 9999
Default:
0.0
See also:
A058, A061
32
Table 9.2 – On/Off Points for the Opto Outputs
A058 & A061 Setting
A059 & A062 Range
6 (Above Freq)
0 to 400 Hz
7 (Above Cur)
0 to 180%
8 (Above DCVolt)
0 to 815 V
10 (Above Anlg V)
0 to 100%
16 (Timer Out)
0.1 to 9999 seconds
17 (Counter Out)
1 to 9999 counts
18 (Above PF Ang)
1 to 180 degrees
20 (ParamControl)
0, 1
A064 Opto Out Logic
Range:
0 to 3 (see table 9.3)
Default:
0
See also:
N/A