Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 70

Advertising
background image

9-16

MD65 AC Drive User Manual

21 = NonRec Fault: Value set in Auto Rstrt Tries (A092) is
exceeded, Auto Rstrt Tries (A092) is not enabled, or a
non-resettable fault has occurred.

22 = EM Brk Cntrl: EM brake is energized. Program EM Brk Off
Delay (A160) and EM Brk On Delay (A161) for desired action.

Determines the on/off point for the opto outputs when Opto Outx Sel
(A058 or A061) is set to option 6, 7, 8, 10, 16, 17, 18, or 20. Refer to
table 9.2.

Determines the logic (Normally Open/NO or Normally Closed/NC)
of the opto outputs. Refer to table 9.3.

A059
A062

Opto Out1 Level
Opto Out2 Level

Range:

0.0 to 9999

Default:

0.0

See also:

A058, A061

32

Table 9.2 – On/Off Points for the Opto Outputs

A058 & A061 Setting

A059 & A062 Range

6 (Above Freq)

0 to 400 Hz

7 (Above Cur)

0 to 180%

8 (Above DCVolt)

0 to 815 V

10 (Above Anlg V)

0 to 100%

16 (Timer Out)

0.1 to 9999 seconds

17 (Counter Out)

1 to 9999 counts

18 (Above PF Ang)

1 to 180 degrees

20 (ParamControl)

0, 1

A064 Opto Out Logic

Range:

0 to 3 (see table 9.3)

Default:

0

See also:

N/A