9-44

MD65 AC Drive User Manual

Sets the time the drive remains at minimum frequency before the
relay or an opto is energized and the drive ramps to the
commanded frequency.

The relay or opto is typically connected to a user-supplied
electromechanical brake coil relay. Set Stop Mode (P037) to 8
“Ramp+EM B,CF” or 9 “Ramp+EM Brk” to enable the
electromechanical brake option.

Set Relay Out Sel (A055) and Opto Outx Sel (A058 or A061) to 22
“EM Brk Cntrl” to control brake operation.

Sets the time the drive remains at minimum frequency before the
relay or an opto output is de-energized and the drive stops.

A160 EM Brk Off Delay

Range:

0.01 to 10.00 sec

Default:

2.0 sec

See also:

P037

Figure 9.14 – EM BRK Off Delay

Frequency

Time

Minimum Freq

A160 [EM Brk Off Delay]

A161 [EM Brk On Delay]

Stop

Commanded

Start

Commanded

EM Brk

De-Energized (On)

Drive Stops

EM Brk
Energized (Off)

Ramp Accel

Ram

p D

ecel

A161 EM Brk On Delay

Range:

0.01 to 10.00 sec

Default:

2.0 sec

See also:

P037