9-24
MD65 AC Drive User Manual
Sets the boost voltage (% of Motor NP Volts (P031)) and redefines
the Volts per Hz curve when Boost Select (A084) is set to 0 = Cust
V/Hz, and Torque Perf Mode (A125) is set to 0 = V/Hz.
Sets the frequency where break voltage is applied when Boost
Select (A084) is set to 0 = Custom V/Hz, and Torque Perf Mode
(A125) is set to 0 = V/Hz.
A085 Start Boost
Range:
0.0 to 25.0%
Default:
5.0%
See also:
P031, P032, P034, P035, A084, A086, A087, A088,
A125
Figure 9.8 – Start Boost (A085)
Frequency
Voltage
A087 [Break Frequency]
P032 [Motor NP Hertz]
P035 [Maximum Freq]
A085 [Start Boost]
P031 [Motor NP Volts]
A088 [Maximum Voltage]
A086 [Break Voltage]
A034 [Minimum Freq]
A086 Break Voltage
Range:
0.0 to 100.0%
Default:
25.0%
See also:
P031, P032, P034, P035, A084, A085, A087, A088,
A125