9-24

MD65 AC Drive User Manual

Sets the boost voltage (% of Motor NP Volts (P031)) and redefines
the Volts per Hz curve when Boost Select (A084) is set to 0 = Cust
V/Hz, and Torque Perf Mode (A125) is set to 0 = V/Hz.

Sets the frequency where break voltage is applied when Boost
Select (A084) is set to 0 = Custom V/Hz, and Torque Perf Mode
(A125) is set to 0 = V/Hz.

A085 Start Boost

Range:

0.0 to 25.0%

Default:

5.0%

See also:

P031, P032, P034, P035, A084, A086, A087, A088,
A125

Figure 9.8 – Start Boost (A085)

Frequency

Voltage

A087 [Break Frequency]

P032 [Motor NP Hertz]

P035 [Maximum Freq]

A085 [Start Boost]

P031 [Motor NP Volts]

A088 [Maximum Voltage]

A086 [Break Voltage]

A034 [Minimum Freq]

A086 Break Voltage

Range:

0.0 to 100.0%

Default:

25.0%

See also:

P031, P032, P034, P035, A084, A085, A087, A088,
A125