9-34

MD65 AC Drive User Manual

Scales the time value when the drive is running at Maximum Freq
(P035). When set to a value other than zero, Process Display
(d010) indicates the duration of the process.

Disables the bus regulator.

Maximum output current allowed before current limiting occurs. This
parameter is only active if Digital Inx Sel (A051-A054) is set to 25 =
Current Lmt2 and is active.

Sets the center of a frequency band at which the drive will not
operate continuously (also called an avoidance frequency). A
setting of 0 disables this parameter.

Determines the bandwidth around Skip Frequency (A119); half the
band above and half the band below the skip frequency. Refer to
figure 9.12.

A116 Process Time Hi

Range:

0.00 to 99.99

Default:

0.00

See also:

d010, P035

A117 Bus Reg Mode

Range:

0 = Disabled
1 = Enabled

Default:

1 = Enabled

See also:

N/A

A118 Current Limit 2

Range:

0.1 to Drive Rated Amps x 1.8

Default:

Drive Rated Amps x 1.8

See also:

P033, A051-A054, A089

A119 Skip Frequency

Range:

0 to 400 Hz

Default:

0 Hz

See also:

A120

A120 Skip Freq Band

Range:

0.0 to 30.0 Hz

Default:

0.0 Hz

See also:

A119