Rockwell Automation MD65 User Manual Version 2.0 User Manual
Page 42

6-8
MD65 AC Drive User Manual
3-Wire SNK Control -
Non-Reversing
Internal Supply (SNK)
3-Wire SRC Control -
Reversing
P036 (Start Source) =
1
A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by P037
(Stop Mode). I/O
Terminal 03
determines direction.
Internal Supply (SRC)
External Supply (SRC)
3-Wire SNK Control -
Reversing
Internal Supply (SNK)
Opto-Output (1 & 2)
A058 (Opto Out1 Sel)
determines Opto-
Output 1 (I/O Terminal
17) operation.
A061 (Opto Out2 Sel)
determines Opto-
Output 2 (I/O Terminal
18) operation.
When using Opto-
Output with an
inductive load such as
a relay, install a
recovery diode parallel
to the relay as shown,
to prevent damage to
the output.
Opto-Output 1
Input/Output
Connection Example
Stop
Start
01
02
03
04
11
01
02
03
Stop
Start
Direction
+24V
Common
Stop
Start
Direction
01
02
03
04
Each digital input draws 6 mA.
Stop
Start
Direction
01
02
03
04
Common
+24V
CR
09
17
Each Opto-Output is rated
30 VDC 50 mA (Non-inductive).