Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 42

Advertising
background image

6-8

MD65 AC Drive User Manual

3-Wire SNK Control -
Non-Reversing

Internal Supply (SNK)

3-Wire SRC Control -
Reversing
P036 (Start Source) =
1

A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by P037
(Stop Mode). I/O
Terminal 03
determines direction.

Internal Supply (SRC)

External Supply (SRC)

3-Wire SNK Control -
Reversing

Internal Supply (SNK)

Opto-Output (1 & 2)

A058 (Opto Out1 Sel)
determines Opto-
Output 1 (I/O Terminal
17) operation.
A061 (Opto Out2 Sel)
determines Opto-
Output 2 (I/O Terminal
18) operation.

When using Opto-
Output with an
inductive load such as
a relay, install a
recovery diode parallel
to the relay as shown,
to prevent damage to
the output.

Opto-Output 1

Input/Output

Connection Example

Stop

Start

01

02

03

04

11

01

02

03

Stop

Start

Direction

+24V

Common

Stop

Start

Direction

01

02

03

04

Each digital input draws 6 mA.

Stop

Start

Direction

01

02

03

04

Common

+24V

CR

09

17

Each Opto-Output is rated
30 VDC 50 mA (Non-inductive).