10.2.7 Problem: Drive Will Not Reverse Motor

Direction.

10.2.8 Problem: Drive Does Not Power Up

Table 10.7 – Problem: Drive Will Not Reverse Motor Direction

Cause(s)

Indication

Corrective Action

Digital input is not selected
for reversing control.

None

Check Digital Inx Sel. Choose
correct input and program for
reversing mode.

Digital input is incorrectly
wired.

None

Check input wiring.

Motor wiring is improperly
phased for reverse.

None

Switch two motor leads.

Reverse is disabled.

None

Check Reverse Disable
(A095).

Cause(s)

Indication

Corrective Action

No input power to the drive.

None

Check the power circuit.

Check the supply voltage.

Check all fuses and
disconnects.

Jumper between I/O
Terminals P2 and P1 not
installed and/or DC Bus
Inductor not connected.

None

Install jumper or connect DC
Bus Inductor.