Parameter Descriptions

9-15

Important:

The value for A059 or A062 must be entered in
percent of drive rated output current.

7 = Above Cur: Drive exceeds the current (% Amps) value set in
Opto Outx Level (A059 or A062). Use A059 or A062 to set the
threshold.

Important:

Value for Opto Outx Level (A059 or A062) must be
entered in percent of drive rated output current.

8 = Above DCVolt: Drive exceeds the DC bus voltage value set in
Opto Outx Level (A059 or A062). Use A059 or A062 to set the
threshold.

9 = Retries Exst: The value set in Auto Rstrt Tries (A092) is
exceeded.

10 = Above Anlg V: The analog input voltage (I/O Terminal 13)
exceeds the value set in Relay Out Level (A056). Do not use if 10 V
Bipolar Enbl (A123) is set to 1 = Bi-Polar In.

11 = Logic In 1: An input is programmed as Logic In 1 and is active.

12 = Logic In 2: An input is programmed as Logic In 2 and is active.

13 = Logic 1 & 2: Both logic inputs are programmed and active.

14 = Logic 1 or 2: One or both logic inputs are programmed and
one or both is active.

15 = StpLogic Out: Drive enters StepLogic

TM

step with digit 3 of

the Command Word (A140-A147) set to enable the StepLogic

TM

output.

16 = Timer Out: The timer has reached the value set in Opto Outx
Level (A059 or A062). Use A059 or A062 to set the threshold.

17 = Counter Out: The counter has the reached the value set in
Opto Outx Level (A059 or A062). Use A059 or A062 to set the
threshold.

18 = Above PF Ang: The Power Factor angle has exceeded the
value set in Opto Outx Level (A059 or A062). Use A059 or A062 to
set the threshold.

19 = Anlg In Loss: An analog input loss has occurred. Program
Analog In Loss (A122) for action desired when input loss occurs.

20 = ParamControl: Enables the output to be controlled over
network communications by writing to Opto Outx Level (A059 to
A062). (0=Off, 1=On)