I-6

MD65 AC Drive User Manual

PID Preload

The value set in PID Preload (A139), in Hertz, will be pre-loaded
into the integral component of the PID at any start or enable. This
will cause the drive’s frequency command to initially jump to that
preload frequency, and the PID loop starts regulating from there.

PID Limits

PID Trim Hi (A130) and PID Trim Lo (A131) are used to limit the PID
output and are only used in trim mode. PID Trim Hi (A130) sets the
maximum frequency for the PID output in trim mode. PID Trim Lo
(A131) sets the reverse frequency limit for the PID output in trim
mode. Note that when the PID reaches the Hi or Lo limit, the PID
regulator stops integrating so that windup does not occur.

PID Enabled

Freq Cmd

PID Output

PID Pre-load Value

PID Pre-load Value > 0