Parameter Descriptions

9-25

Sets the frequency where the break frequency is applied when
Boost Select (A084) is set to 0 = Custom V/Hz, and Torque Perf
Mode (A125) is set to 0 = V/Hz.

Sets the highest voltage the drive will output.

Maximum output current allowed before current limiting occurs.

The drive provides Class 10 motor overload protection. Settings 0-2
select the derating factor for the I

2

t overload function. See figure

9.9.

A087 Break Frequency

Range:

0.0 to 400.0 Hz

Default:

15.0 Hz

See also:

P031, P032, P034, P035, A084, A085, A086, A088,
A125

A088 Maximum Voltage

Range:

20 to Drive Rated Volts

Default:

Drive Rated Volts

See also:

d004, A085, A086, A087

A089 Current Limit 1

Range:

0.1 to (Drive Rated Amps x 1.8)

Default:

Drive Rated Amps x 1.8

See also:

P033, A118

A090 Motor OL Select

Range:

0 = No Derate
1 = Min Derate
2 = Max Derate

Default:

0 = No Derate

See also:

P032

Figure 9.9 – Motor OL Select (A090)

Min Derate

0

80

100

60

40

20

No Derate

0

80

100

60

40

20

%

of P033

[Motor OL Curent

]

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25