Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 94

Advertising
background image

9-40

MD65 AC Drive User Manual

Sets the value of the PID integral component when the PID mode is
enabled by PID Ref Select (A132).

Sets the value for the PID differential component when the PID
mode is enabled by PID Ref Select (A132).

Provides an internal fixed value for the process setpoint when the
PID mode is enabled by PID Ref Select (A132).

Sets the lower limit of the PID output.

Sets the value used to preload the integral component on start or
enable.

A135 PID Integ Time

Range:

0.0 to 999.9 sec

Default:

0.0 sec

See also:

N/A

A136 PID Diff Rate

Range:

0.00 to 99.99 (1/sec)

Default:

0.00 (1/sec)

See also:

N/A

A137 PID Setpoint

Range:

0.0 to 100.0%

Default:

0.0%

See also:

N/A

A138 PID Deadband

Range:

0.0 to 10.0%

Default:

0.0%

See also:

N/A

A139 PID Preload

Range:

0.0 to 400.0 Hz

Default:

0.0 Hz

See also:

N/A