MD65 AC Drive User Manual

PID Feedback Sel (A133) is used to select the source of the PID
feedback.

Table I.2 – PID Feedback Sel (A133) Options

Analog PID Reference Signals

Parameters Anlg ln 0-10V Lo (A110) and Anlg ln 0-10V Hi (A111)
are used to scale or invert an analog PID Reference.

Important: Firmware version FRN 1.xx does not support

PID Feedback scaling from an analog input.

Examples

Scale Function

For a 0-5 volt signal, the following parameter settings are used so
that a 0 volt signal = 0% PID Reference and a 5 volt signal = 100%
PID Reference.

Angl ln 0-10V Lo (A110) = 0.0%

Angl ln 0-10V Hi (A111) = 50.0%

PID Ref Sel (A132) = 0 “0-10V Input”

Option

Description

0 “0-10V Input”

Selects the 0-10V Input (default setting). Note that the PID will
not function with a bipolar analog input. It will ignore any
negative voltages and treat them like a zero.

1 “4-20mA Input“

Selects the 4-20mA Input.

2 “Comm Port”

The reference word from a communication network such as
Modbus RTU or DeviceNet becomes the PID Feedback. The
value sent over the network is scaled so that P035 [Maximum
Freq] x 10 = 100% Feedback. For example, with [Maximum
Freq] = 60 Hz, a value of 600 sent over the network would
represent 100% Feedback.

0

10

20

30

40

50

60

70

80

90 100

PID Reference (%)

Input V

olts

2

4

6

8

10

12