Parameter Descriptions

9-35

A setting of 0 disables this parameter.

Sets the time that the drive will remain in stall mode before a fault is
issued.

Figure 9.12 – Skip Freq Band (A120)

Frequency

Time

Skip Frequency

Command

Frequency

Drive Output
Frequency

2x Skip
Frequency Band

A121 Stall Fault Time

Range:

0 = 60 sec
1 = 120 sec
2 = 240 sec
3 = 360 sec
4 = 480 sec
5 = Flt Disabled

Default:

0 = 60 sec

See also:

A089-A118

A122 Analog In Loss

Range:

0 = Disabled
1 = Fault (F29)
2 = Stop
3 = Zero Ref
4 = Min Freq Ref
5 = Max Freq Ref
6 = Int Freq Ref

Default:

0 = Disabled

See also:

A110, A111, A132