Rockwell Automation MD65 User Manual Version 2.0 User Manual
Page 86

9-32
MD65 AC Drive User Manual
Sets the percentage of output desired by the user. If this is enabled
via Analog Out Sel (A065), this determines the analog value that is
output from the analog output (V or mA).
Sets the analog input level that corresponds to Minimum Freq
(P034) if a 0-10V input is used by Speed Reference (P038).
Setting this value larger than Anlg In 0-10V Hi (A111) inverts the
analog signal.
Sets the analog input level that corresponds to Maximum Freq
(P035) if a 0-10 V input is used by Speed Reference (P038).
Setting this value smaller than Anlg In 0-10V Lo (A110) inverts the
analog signal.
A109 Anlg Out Setpoint
Range:
0.0 to 100%
Default:
0.0%
See also:
A065
A110 Anlg In 0-10V Lo
Range:
0.0 to 100.0%
Default:
0.0%
See also:
d020, P034, P038, A122
Figure 9.11 – Anlg In 0-10V Lo (A110)
0
P035 [Maximum Freq]
P034 [Minimum Freq]
A110 [Anlg In 0-10V Lo]
A111 [Anlg In 0-10V Hi]
0
Speed Reference
A111 Anlg In 0-10V Hi
Range:
0.0 to 100.0%
Default:
100.0%
See also:
d020, P035, P038, A122, A123