9-22

MD65 AC Drive User Manual

Enables/disables external dynamic braking.

Sets the percentage of acceleration or deceleration time that is
applied to the ramp as an S Curve. Time is added, 1/2 at the
beginning and 1/2 at the end of the ramp.

For example: If Accel Time = 10 seconds, and the S Curve %
setting is 50%, the S Curve time will be 10 x 0.5 = 5 seconds. The
total time will be 10 + 5 = 15 seconds.

See figure 9.6 for an example.

A082 DB Resistor Sel

Range:

0 = Disabled
1 =

Normal RA Resistor (5% Duty Cycle)

2 = No Protection (100% Duty Cycle)
3 to 99 = Duty Cycle Limited (3% to 99% Duty
Cycle)

Default:

0 = Disabled

See also:

P037

A083 S Curve %

Range:

0 to 100%

Default:

0% (Disabled)

See also:

N/A

Accel Time = 10 sec

S Curve% = 50%

S Curve Time = 10 x 0.5 = 5 sec

Total Time = 10 + 5 = 15 sec

Figure 9.6 – S Curve % (A083) Example

1/2 S Curve Time

2.5 Seconds

Total Time to Accelerate = Accel Time + S Curve Time

50% S Curve

Target

Target/2

Accel Time

10 Seconds

1/2 S Curve Time

2.5 Seconds