Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 60

Advertising
background image

9-6

MD65 AC Drive User Manual

4 = Preset Freq: External frequency command as defined by
Preset Freq x (A070-A077) when Digital Inx Sel (A051-A054) are
programmed as “Preset Frequencies,” and the digital inputs are
active.

5 = Comm Port: External frequency command from the
communications port.

6 = Stp Logic: External frequency command as defined by Preset
Freq x (A070-A077) and Stp Logic x (A140-A147).

7 = Anlg ln Mult: External frequency command as defined by the
product of the analog inputs (shown in Analog ln 0-1-V (d020) and
Analog ln 4-20mA (d021). [Analog ln 0-10V] x [Analog ln 4-20mA] =
Speed Command

Example: 100% x 50% = 50%

Sets the rate of acceleration for all speed increases. See figure 9.1.

Maximum Frequency / Accel Time = Accel Rate

Sets the rate of deceleration for all speed decreases. See figure 9.2.

P039 Accel Time 1

Range:

0.0 to 600.0 sec

Default:

5.0 sec

See also:

P038, P040, A051-A054, A067, A070-A077,
A140-A147

Figure 9.1 – Accel Time 1 (P039)

P040 Decel Time 1

Range:

0.1 to 600.0 sec

Default:

5.0 sec

See also:

P038, P039, A051-A054, A068, A070-A077,
A140-A147

Speed

0

Time

P035 [Maximum Freq]

P039 or A067

[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceleration

D

ecel

era

tion