MD60 AC Drive User Manual

Essential Requirements for CE Compliance

The following conditions must be satisfied for MD65 drives to meet
the requirements of EN61800-3.

Grounding as described in figure D.1. Refer to chapter 4 for
additional grounding recommendations.

Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit
or equivalent attenuation.

Allowable cable length in table D.1 is not exceeded.

Table D.1 – Allowable Cable Length

Filter Type

EN61800-3

First Environment

Restricted Distribution

or Second

Environment

2

EN61800-3

First Environment

Unrestricted

Distribution

3

Integral

10 meters (33 feet)

1 meter (3 feet)

External - Short

1

10 meters (33 feet)

1 meter (3 feet)

External - Long

1

100 meters (328 feet)

5 meters (16 feet)

1

Contact Reliance Electric for details on optional external filters.

2

Equivalent to EN55011 Class A.

3

Equivalent to EN55011 Class B.

Figure D.1 – Connections and Grounding

R/L1
S/L2

T/L3

U/T1
V/T2

W/T3

EMI Fittings and Metal Conduit

IP 30/NEMA 1/UL Type 1
Option Kit

Shielded Enclosure

(1)

Building Structure Steel

Enclosure Ground Connection

(2)

EMI Filter

L1'

L2'

L3'

L1

L2

L3

Shielded Motor Cable

(1) First Environment Unrestricted Distribution installations require a

(2) Integral EMI filters are available on 240 V, 1-phase drives.

shielded enclosure. Keep wire length as short as possible between

the enclosure entry point and the EMI filter.

NEMA 1/IP30 Kit