Installing Control Wiring

6-11

6.6

Accel/Decel Selection

The selection of Accel/Decel rates can be made through digital
inputs, RS485 communications and/or parameters. See figure 6.3.

Figure 6.3 – Accel/Decel Selection

No

Yes

No

RS485 Port

Controls Speed

No

Yes

Drive Stopped
(Not Running)

Yes

Either

P039 (Accel Time 1)/P040 (Decel Time 1)

or

A067 (Accel Time 2)/A068 (Decel Time 2)

can be selected when

RS485 port is active.

Input is programmed

as "Accel 2 & Decel 2"

A051, A052, A053

or A054 = 1

No

Yes

A067 (Accel Time 2)/A068 (Decel Time 2)

is active when input is active.

Speed is controlled

by (Preset Freq x)

No

Yes

P039 (Accel Time 1)/P040 (Decel Time 1);

A067 (Accel Time 2)/A068 (Decel Time 2)

determined by the active

Preset Frequency.

See A070-A077 (Preset Freq 0-7)

Either

P039 (Accel Time 1)/P040 (Decel Time 1)

or

A067 (Accel Time 2)/A068 (Decel Time 2)

can be selected by the Digit 3 setting

of the Step Logic parameters.

See A140-A147 (Stp Logic 0-7)

Speed is controlled

by Stp Logic

No

Yes

P039 (Accel Time 1)/P040 (Decel Time 1)

are used.

Drive will Start and Run

at Jog Speed.

Drive will use A079 (Jog Accel/Decel)

Jog Input

Enabled and Active:

A051, A052, A053
or A054 = 2, 11,12