Parameter Descriptions

9-49

Displays the status of the control terminal block control inputs.

Important:

Actual control commands may come from a source
other than the control terminal block.

Displays the status of the control terminal block digital inputs.

d013 Contrl In Status

Range:

0 = Input Present
1 = Input Not Present
See figure 9.17

Default:

Read Only

See also:

d002, P034, P035

Figure 9.17 – Contrl In Status (d013) Bit Definitions

1 = Input Present, 0 = Input Not Present

Start / Run FWD Input (I/O Terminal 02)

Bit 0

Direction / Run REV Input (I/O Terminal 03)

Bit 1

Stop Input

1

(I/O Terminal 01)

Bit 2

1

The stop input must be present in order to start the drive.

When this bit is a 1, the drive can be started.
When this bit is a 0, the drive will stop.

Dynamic Brake Transistor On

Bit 3

d014 Dig In Status

Range:

0 = Input Not Present
1 = Input Present
See figure 9.18.

Default:

Read Only

See also:

A051-A054

Figure 9.18 – Dig In Status (d014) Bit Definitions

Digital In1 Sel (I/O Terminal 05)

Bit 0

Digital In2 Sel (I/O Terminal 06)

Bit 1

Digital In3 Sel (I/O Terminal 07)

Bit 2

Digital In4 Sel (I/O Terminal 08)

Bit 3