Troubleshooting the Drive
10-9
10.2.4 Problem: Motor Does Not Start
Cause(s)
Indication
Corrective Action
No output voltage to the
motor.
None
Check the power circuit.
•
Check the supply voltage.
•
Check all the fuses and
disconnects.
Check the motor.
•
Verify that the motor is
connected properly.
Check the control input
signals
•
Verify that a Start signal is
present. If 2-Wire control
is used, verify that either
the Run Forward or Run
Reverse signal is active,
but not both.
•
Verify that I/O Terminal 01
is active.
•
Verify that Start Source
(P036) matches your
configuration.
•
Verify that Reverse
Disable (A095) is not
prohibiting movement.
Drive is faulted.
Flashing red
STATUS LED.
Clear fault.
•
Press Stop
•
Cycle power
•
Set Fault Clear (A100) to
1 = Clear Faults.
•
Cycle digital input if Digital
Inx Sel (A051-A054) is set
to 7 = Clear Fault.