Troubleshooting the Drive

10-9

10.2.4 Problem: Motor Does Not Start

Cause(s)

Indication

Corrective Action

No output voltage to the
motor.

None

Check the power circuit.

•

Check the supply voltage.

•

Check all the fuses and
disconnects.

Check the motor.

•

Verify that the motor is
connected properly.

Check the control input
signals

•

Verify that a Start signal is
present. If 2-Wire control
is used, verify that either
the Run Forward or Run
Reverse signal is active,
but not both.

•

Verify that I/O Terminal 01
is active.

•

Verify that Start Source
(P036) matches your
configuration.

•

Verify that Reverse
Disable (A095) is not
prohibiting movement.

Drive is faulted.

Flashing red
STATUS LED.

Clear fault.

•

Press Stop

•

Cycle power

•

Set Fault Clear (A100) to
1 = Clear Faults.

•

Cycle digital input if Digital
Inx Sel (A051-A054) is set
to 7 = Clear Fault.