MD65 AC Drive User Manual

level programmed to the desired number of counts. When the
counter reaches the count programmed into the output level the
output will change state. The counter can be reset via a digital
input programmed as “Reset Counter”.

StepLogic

TM

Using Timed Steps

To activate this function, set Speed Reference (P038) to 6 “Stp
Logic”. Three parameters are used to configure the logic, speed
reference and time for each step.

Logic is defined using Stp Logic x parameters (A140-A147).

Preset Speeds are set with Preset Freq x parameters
(A070-A077).

Time of operation for each step is set with Stp Logic Time x
parameters (A150-A157).

The direction of motor rotation can be forward or reverse.

StepLogic

TM

Sequence

Sequence begins with a valid start command.

A normal sequence begins with Step 0 and transition to the
next step when the corresponding StepLogic

TM

time has

expired.

Step 7 is followed by Step 0

Sequence repeats until a stop is issued or a fault condition
occurs.

Figure H.1 – Using Timed Steps

Time

0

Forward

Reverse

Step 0

Step 1

Step 2

Step 3 Step 4 Step 5 Step 6

Step 7