Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 120

Advertising
background image

A-2

MD65 AC Drive User Manual

Accel/Decel:

Two independently programmable accel and decel
times. Each time may be programmed from 0-600
seconds in 0.1 second increments.

Intermittent
Overload:

• 150% Overload capability for up to 1 minute.

• 200% Overload capacity for up to 3 seconds

Electronic Motor
Overload Protection:

Class 10 protection with speed-sensitive response.

Input/Output Rating

Output Frequency:

0-400 Hz (Programmable)

Efficiency:

97.5% (Typical)

Digital Control Inputs (Inputs Current = 6 mA)

SRC (Source)
Mode:

18-24 V = ON
0-6 V = OFF

SNK (Sink) Mode:

0-6 V = ON
18-24 V = OFF

Analog Control Inputs

4-20 mA Analog:

250 ohm input impedance

0-10 V DC Analog:

100k ohm input impedance

External Pot:

1-10 k ohm, 2 Watt minimum

Control Output

Programmable Output (form C relay)

Resistive Rating:

3.0 A at 30 V DC, 3.0 A at 125 V AC, 3.0 A at
240 V AC

Inductive Rating:

0.5 A at 30 V DC, 0.5 A at 125 V AC, 0.5 A

Opto Outputs

Resistive Rating:

30 V DC, 50 mA

Inductive Rating:

Recover diode. Refer to figure 6.1 for details.

Analog Outputs (10-bit)

Rating:

0-10 V, 1k ohm min.
4-20 mA, 525 ohm max

Fuses and Circuit Breakers

Recommended
Fuse Type:

UL Class J, CC, T or Type BS88; 600 V (550 V) or
equivalent.

Recommended
Circuit Breakers:

HMCP circuit breakers or equivalent.