Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 65

Advertising
background image

Parameter Descriptions

9-11

Sets the condition that changes the state of the output relay
contacts.

0 = Ready/Fault (Default): Relay changes state when power is
applied. This indicates that the drive is ready for operation. Relay
returns drive to shelf state when power is removed or a fault occurs.

1 = At Frequency: Drive reaches commanded frequency.

2 = MotorRunning: Motor is receiving power from the drive.

3 = Reverse: Drive is commanded to run in reverse direction.

4 = Motor Overload: Motor overload condition exists.

5 = Ramp Reg: Ramp regulator is modifying the programmed
accel/decel times to avoid an overcurrent or overvoltage fault.

6 = Above Freq: Drive exceeds the frequency (Hz) value set in
Relay Output Level (A056). Use A056 to set the threshold.

7 = Above Cur: Drive exceeds the current (% Amps) value set in
Relay Output Level (A056). Use A056 to set the threshold.

Important:

The value for Relay Output Level must be entered in
percent of drive rated output current.

A055 Relay Out Sel

Range:

0 = Ready/Fault
1 = At Frequency
2 = MotorRunning
3 = Reverse
4 = Motor Overld
5 = Ramp Reg
6 = Above Freq
7 = Above Cur
8 = Above DCVolt
9 = Retries Exst
10 = Above Anlg V
11 - Logic In 1
12 = Logic In 2
13 = Logic 1 & 2
14 = Logic 1 or 2
15 = StpLogic Out
16 = Timer Out
17 = Counter Out
18 = Above PF Ang
19 = Anlg In Loss
20 = ParamControl
21 = NonRec Fault
22 = EM Brk Cntrl

Default:

0 = Ready/Fault

See also:

P033, A056, A092, A140-A147, A150-A157

Advertising