Parameter Descriptions

9-17

Sets the analog output signal mode (0-10 V, 0-20 mA, or 4-20 mA).
The output is used to provide a signal that is proportional to several
drive conditions.

Table 9.3 – A064 Options

A064 Option

Opto Out1 Logic

Opto Out2 Logic

0

NO (Normally Open)

NO (Normally Open)

1

NC (Normally Closed)

NO (Normally Open)

2

NO (Normally Open)

NC (Normally Closed)

3

NC (Normally Closed)

NC (Normally Closed)

A065 Analog Out Sel

Range:

0 to 20

Default:

0

See also:

A066, P035

Table 9.4 – Analog Output Signal Mode Selections

Option

Output

Range

Minimum

Output Value

Maximum Output Value

A066 (Analog Out High)

DIP

Switch

Position

0 = OutFreq 0-10

0-10 V

0 V = 0 Hz

P035 (Maximum Freq)

0-10 V

1 = OutCurr 0-10

0-10 V

0 V = 0 Amps

200% Drive Rated Output Current 0-10 V

2 = OutVolt 0-10

0-10 V

0 V = 0 Volts

120% Drive Rated Output Volts

0-10 V

3 = OutPowr 0-10

0-10 V

0 V = 0 kW

200% Drive Rated Power

0-10 V

4 = TstData 0-10

0-10 V

0 V = 0000

65535 (Hex FFFF)

0-10 V

5 = OutFreq 0-20

0-20 mA 0 mA = 0 Hz

P035 (Maximum Freq)

0-20 mA

6 = OutCurr 0-20

0-20 mA 0 mA = 0 Amps 200% Drive Rated Output Current 0-20 mA

7 = OutVolt 0-20

0-20 mA 0 mA = 0 Volts

120% Drive Rated Output Volts

0-20 mA

8 = OutPowr 0-20

0-20 mA 0 mA = 0 kW

200% Drive Rated Power

0-20 mA

9 = TstData 0-20

0-20 mA 0 mA = 0000

65535 (Hex FFFF)

0-20 mA

10 = OutFreq 4-20 4-20 mA 4 mA = 0 Hz

P035 (Maximum Freq)

0-20 mA

11 = OutCurr 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated Output Current 0-20 mA
12 = OutVolt 4-20

4-20 mA 4 mA = 0 Volts

120% Drive Rated Output Volts

0-20 mA

13 = OutPowr 4-20 4-20 mA 4 mA = 0 kW

200% Drive Rated Power

0-20 mA

14 = TstData 4-20 4-20 mA 4 mA = 0000

65535 (Hex FFFF)

0-20 mA

15 = OutTorq 0-10 0-10 V

0V = 0 Amps

200% Drive Related FLA

0-10 V

16 = OutTorq 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Related FLA

0-20 mA

17 = OutTorq 4-20 4-20 mA 4 mA = 0 Amp

200% Drive Related FLA

0-20 mA

18 = Setpnt 0-10

0-10 V

0V = 0%

100.0% Setpoint Setting

0-10 V

19 = Setpnt 0-20

0-20 mA 0 mA = 0%

100.0% Setpoint Setting

0-20 mA

20 = Setpnt 4-20

4-20 mA 4 mA = 0%

100.0% Setpoint Setting

0-20 mA