MD65 AC Drive User Manual

8 = Above DCVolt: Drive exceeds the DC bus voltage value set in
Relay Output Level (A056). Use A056 to set the threshold.

9 = Retries Exst: Number of retries set in Auto Rstrt Tries (A092) is
exhausted.

10 = Above Anlg V: The analog input voltage (I/O Terminal 13)
exceeds the value set in Relay Out Level (A056). Do not use if 10V
Bipolar Enbl (A123) is set to 1 = Bi-Polar In.

11 = Logic In 1: An input is programmed as Logic In 1 and is active.

12 = Logic In 2: An input is programmed as Logic In 2 and is active.

13 = Logic 1 & 2: Both logic inputs are programmed and active.

14 = Logic 1 or 2: One or both logic inputs are programmed and
one or both is active.

15 = StpLogic Out: Drive enters StepLogic

TM

step with digit 3 of

the Command Word (A140-A147) set to enable the StepLogic

TM

output.

16 = Timer Out: The timer has reach the value set in Relay Out
Level (A056). Use A056 to set the threshold.

17 = Counter Out: The counter has reached the value set in Relay
Out Level (A056). Use A056 to set the threshold.

18 = Above PF Ang: The Power Factor angle has exceeded the
value set in Relay Out Level (A056). Use A056 to set the threshold.

19 = Anlg In Loss: Analog input loss has occurred. Program
Analog In Loss (A122) for the desired action when input loss occurs.

20 = ParamControl: Enables the output to be controlled over
network communications by writing to Relay Out Level (A056).
0 = Off, 1 = On.

21 = NonRec Fault: Value set in Auto Rstrt Tries (A092) is
exceeded, Auto Rstrt Tries (A092) is not enabled, or a
non-resettable fault has occurred.

22 = EM Brk Cntrl: EM brake is energized. Program EM Brk Off
Delay (A160) and EM Brk On Delay (A161) for desired action.