Ppendix, Rs485 (mdi) protocol – Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 149

Advertising
background image

RS485 (MDI) Protocol

F-1

A

PPENDIX

F

RS485 (MDI)

Protocol

MD65 drives support the RS485 (MDI) protocol to allow efficient
operation with Rockwell Automation peripherals. In addition, some
Modbus functions are supported to allow simple networking. MD65
drives can be multi-dropped on an RS485 network using Modbus
protocol in RTU mode.

For information regarding DeviceNet or other communication
protocols, refer to the appropriate user manual.

Network Wiring

Network wiring consists of a shielded 2-conductor cable that is
daisy-chained from node to node. See figure F.2.

Only pins 4 and 5 on the RJ45 plug should be wired. The other pins
on the MD65 RJ45 socket contain power, etc., for other Rockwell
Automation peripheral devices and must not be connected.

Figure F.1 – Sample Network

Controller

Figure F.2 – Network Wiring Diagram

Master

MD65 Drive

Node 1

4

5

MD65 Drive

Node 2

4

5

MD65 Drive

Node "n"

4

5

TxRxD+

TxRxD-

TxRxD+

TxRxD-

TxRxD+

TxRxD-

NOTE: The shield is connected at ONLY ONE end of each cable segment.

Shield

Shield

Shield

120 ohm resistor

120 ohm resistor

X

X

X

FRONT

PIN 8

PIN 1

Advertising