Parameter Descriptions

9-23

Sets the boost voltage (% of Motor NP Volts (P031)) and redefines
the Volts per Hz curve. Active when Torque Perf Mode (A125) is set
to 0 = V/Hz. Note that the drive may add additional voltage unless
option 5 is selected. See figure 9.7.

A084 Boost Select

Range:

0 = Custom V/Hz

Variable Torque (typical fan/pump curves):
1 = 30.0, VT
2 = 35.0, VT
3 = 40.0, VT
4 = 45.0, VT

Constant Torque:
5 = 0.0 no IR Compensation
6 = 0.0
7 = 2.5, CT
8 = 5.0, CT
9 = 7.5, CT
10 = 10.0, CT
11 = 12.5, CT
12 = 15.0, CT
13 = 17.5, CT
14 = 20.0, CT

Default:

8 = 5.0, CT
7 = 2.5, CT (for 4.0, 5.5, 7.5 kW (5.0, 7.5, and 10.0 HP)
drives only)

See also:

d004, P031, P032, A085-A087, A125

Figure 9.7 – Boost Select (A084)

% P032 [Motor NP Hertz]

% P031 [Motor NP Volts]

100

50

1/2 [Motor NP Volts]

1/2

[Motor NP Hertz]

4
3
2
1

0

50

100

Settings

5-14