5-4

MD65 AC Drive User Manual

5.2.2 Input Power Conditioning

The drive is suitable for direct connection to input power within the
rated voltage of the drive (see table 5.4). Table 5.1 lists certain input
power conditions that may cause component damage or reduction
in product life. If any of the conditions exist, install one of the
devices listed in the “Corrective Action” column in table 5.1 on the
line side of the drive.

Important:

Only one device per branch circuit is required. It
should be mounted closest to the branch and sized to
handle the total current of the branch circuit.

5.3

Power Wiring Specifications

Table 5.1 – Corrective Actions for Input Power Conditions

Input Power Condition

Corrective Action

Low line impedance (less than 1% line
reactance)

Install one of the following:

Line reactor

1

Isolation transformer

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Line has frequent power interruptions

Line has intermittent noise spikes in excess of
6000V (lightning)

Phase-to-ground voltage exceeds 125% of
normal line-to-line voltage

Remove MOV jumper to
ground and install
isolation transformer
with grounded
secondary, if necessary.

Ungrounded distribution system

1

Contact Reliance Electric for application and ordering information.

Table 5.2 – Power Wiring Specifications

Power Wiring Rating

Recommended Copper Wire

Unshielded 600 V, 75

°

C (167

°

F) THHN/

THWN

15 mils insulated, dry location

Shielded 600 V, 90

°

C (194

°

F)

RHH/RHW-2

Belden 29501-29507 or
equivalent

Shielded Tray rated 600 V, 90

°

C (194

°

F)

RHH/RHW-2

Shawflex 2ACD/3ACD or
equivalent