Technical Specifications

A-3

Protective Features

Motor Protection:

Programmable I

2

t overload protection provides Class

10 protection. See parameter P033.

Overcurrent:

200% hardware limit, 300% instantaneous fault

Over Voltage:

• 100-120 V AC Input – Trip occurs at 405 V DC bus

voltage (equivalent to 150 V AC incoming line

• 200-240 V AC Input – Trip occurs at 405 V DC bus

voltage (equivalent to 290 V AC incoming line)

• 380-460 V AC Input – Trip occurs at 810 V DC bus

voltage (equivalent to 575 V AC incoming line)

• 460-600 V AC Input – Trip occurs at 1005 V DC

bus voltage (equivalent to 711 V AC incoming line)

Under Voltage:

• 100-120 V AC Input – Trip occurs at 210 V DC bus

voltage (equivalent to 75 V AC incoming line)

• 200-240 V AC Input – Trip occurs at 210 V DC bus

voltage (equivalent to 150 V AC incoming line

• 380-480 V AC Input – Trip occurs at 390 V DC bus

voltage (equivalent to 275 V AC incoming line)

• 460-600 V AC Input –

If P042=3 “High Voltage” trip occurs at
487 V DC bus voltage (equivalent to
344 V AC incoming line)

If P042=2 “Low Voltage” trip occurs at
390 V DC bus voltage (equivalent to
275 V AC iincoming line)

Control Ride-
Through:

Minimum ride-through is 0.5 sec - typical value 2 sec

Faultless Power
Ride-Through:

100 milliseconds

Dynamic Braking

Internal brake IGBT included with all ratings 0.75 kW (1 HP) and larger.

Approvals

UL

®

LIST

ED 966X

IND

CO N T E Q

UL508C

UL

®

LIST

ED 966X

IND

CO N T E Q

C

CSA 22.2

EMC Directive 89/336

LV:

EN 50178, EN 60204

EMC: EN 61800-3, EN 50081-1, EN 50082-2