Troubleshooting the Drive

10-5

F41

Phase UV
Short

N Excessive current has

been detected
between these two
output terminals.

Check the motor and
drive output terminal
wiring for a shorted
condition.

Replace drive if fault
cannot be cleared.

F42

Phase UW
Short

F43

Phase VW
Short

F48

Params
Defaulted

N The drive was

commanded to write
default values to
EEPROM.

Clear the fault or cycle
power to the drive.

Program the drive
parameters as needed.

F63

SW
OverCurrent

Y Programmed SW

Current Trip (A098)
has been exceeded.

Check load requirements
and SW Current Trip
(A098) setting.

F64

Drive
Overload

N Drive rating of 150%

for 1 minute or 200%
for 3 seconds has been
exceeded.

Reduce load or extend
Accel Time.

F70

Power Unit

N Failure has been

detected in the drive
power section.

Cycle power.

Replace drive if fault
cannot be cleared.

F80

SVC
Autotune

N The Autotune function

was either cancelled
by the user or failed.

Restart procedure.

F81

Comm Loss

N RS485 port stopped

communicating.

If module was not
intentionally
disconnected, check
wiring to the port.
Replace wiring, port
expander, module, or
complete drive as
required.

Check connection.

A module was
intentionally
disconnected.

Turn off using Comm
Loss Action (A105).

Table 10.1 – Fault Descriptions and Corrective Actions (Continued)

No.

Fault

A

uto-Re

set

1

?

Description

Action