MD65 AC Drive User Manual
Reading (03) Feedback
The Feedback (Output Frequency) from the MD65 drive can be
read via the network by sending Function Code 03 reads to register
address 8451 (Feedback).
Table F.6 – Feedback
Feedback
1
1
Returns the same data as Reading (03) Parameter d001 (Output Freq).
Address
(Decimal)
Description
8451
A xxx.x decimal value where the decimal point is fixed. For
example, a decimal “123” equals 12.3 Hz and “300” equals
30.0 Hz.