6-10

MD65 AC Drive User Manual

6.5

Start and Speed Reference Control

The drive speed command can be obtained from a number of
different sources. The source is normally determined by P038
(Speed Reference). However, when A051 or A052 (Digital Inx
Select) is set to option 2, 4, 5, or 6, and the digital input is active,
A051 or A052 will override the speed reference commanded by
P038 (Speed Reference). See figure 6.2 for the override priority.

Figure 6.2 – Override Priority for the Speed Reference Command

Jog Input

Enabled and Active:

A051, A052, A053

or A054 = 2, 11, 12

No

Yes

No

Local/Remote Input

Enabled and Active:

(Digital Inx Sel) = 5

No

Yes

Drive Stopped
(Not Running)

Yes

Drive will Start and Run

at Jog Speed.

Direction comes from

I/O Terminal 03 Dir/Run REV

or

Jog Forward/Jog Reverse command

Start, Speed, and Direction commands

come from Integral Keypad.

Comm Select Input

Enabled and Active:

(Digital Inx Sel) = 6

No

Yes

Start, Speed and Direction commands

come from RS485 (DSI) port.

0-10V Override

Enabled and Active:

(Digital Inx Sel) = 13

No

Yes

Speed commands come from 0-10V.

Start and Direction

follows P036 (Start Source)

or

Bi-Polar input when enabled.

Speed commands come from 4-20mA.

Start and Direction

follows P036 (Start Source).

4-20mA Override

Enabled and Active:

(Digital Inx Sel) = 14

No

Yes

Run as specified by

A071-A077 (Preset Freq 1-7).

Start and Direction commands come

from P036 (Start Source).

A051/A052/A053

Preset Inputs Active

No

Yes

Run as specified by

A132 (PID Ref Select).

Start and Direction commands come

from P036 (Start Source).

PID Enabled:

A132 (PID Ref Select)

0

No

Run as specified by

P038 (Speed Reference).

Start and Direction commands come

from P036 (Start Source).

Yes