2 troubleshooting tables – Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 113

Advertising
background image

Troubleshooting the Drive

10-7

10.2 Troubleshooting Tables

Use the following tables to troubleshoot the drive. If you cannot
resolve the problem using these tables, contact Reliance Electric.

10.2.1 Problem: Drive Does Not Start From Terminal

Block Start or Run Inputs

Table 10.2 – Problem: Drive Does Not Start From Terminal Block Start or Run Inputs

Possible Cause(s)

Indication

Corrective Action

Drive is faulted

Flashing red
FAULT LED

Clear fault by using one of
the following methods:

Press Stop

Cycle power

Set Fault Clear (A100) to
1 = Clear Faults

Cycle digital input if
Digital Inx Sel (A051-
A054) is set to 7 = Clear
Fault

Incorrect programming.

Start Source (P036) is set
to 0 = Keypad or
5 = RS485 Port.

Digital Inx Sel (A051-A054
is set to 5 = Local and the
input is active.

None

Check parameter settings.

Incorrect input wiring. See
section 6.4.1 for wiring
examples.

2-wire control requires
Run Forward, Run
Reverse or Jog input.

3-wire control requires
Start and Stop inputs

Stop input is always
required.

None

Wire inputs correctly and/or
install jumper.

Incorrect Sink/Source DIP
switch setting.

None

Set switch to match wiring
scheme.