Parameter Descriptions

9-3

Sets the control scheme used to start the drive.

Refer to section 6.5, Start and Speed Reference Control, for details
about how other drive settings can override the setting of this
parameter.

Important:

For all settings except option 3, the drive must receive
a leading edge from the start input for the drive to start
after a stop input, loss of power, or fault condition.

0 = Keypad (Default): Integral keypad controls drive operation. I/O
Terminal 01 (Stop) on terminal block = coast to stop. When 0 is
selected, the Reverse key is also active unless disabled by Reverse
Disable (A095).

1 = 3-Wire: I/O Terminal 01 (Stop) = stop according to the value set
in Stop Mode (P037). Refer to section 6.4.1 for wiring examples.

2 = 2-Wire: I/O Terminal 01 (Stop) = coast to stop. Refer to section
6.4.1 for wiring examples.

3 = 2-W Lvl Sens: Two-wire level-sensitive. Drive will restart after a
Stop command when Stop is removed and Start is held active.

4 = 2-W Hi Speed: Two-wire high-speed. Outputs are kept in a
ready-to-run state. The drive will respond to a Start command within
10 ms. I/O Terminal 01 (Stop) = coast to stop.

Important:

There is greater potential voltage on the power output
terminals (U/TI, V/T2, W/T3) when using this option.

5 = Comm Port: Remote communications. I/O Terminal 01 (Stop) =
coast to stop.

P036 Start Source

Range:

0 = Keypad
1 = 3-Wire
2 = 2-Wire
3 = 2-W Lvl Sens
4 = 2-W Hi Speed
5 = Comm Port
6 = Momt FWD/REV

Default:

0 = Keypad

See also:

d012, P037

!

ATTENTION: When Start Source (P036) is set to
3 = 2-W Lvl Sens, and the Run input is maintained,
the Run inputs do not need to be toggled after a Stop
input for the drive to run again. A Stop function is
provided only when the Stop input is active (open).
Failure to observe this precaution could result in
severe bodily injury.