Parameter Descriptions

9-39

Sets the minimum positive value that is added to a PID reference
when PID trim is used.

Enables/Disables PID mode and selects the source of the PID
reference.

Selects the source of the PID feedback. When A133 = 0, the PID
will not function with a bipolar input. Negative voltages are treated
as 0 volts.

Sets the value for the PID proportional component when the PID
mode is enabled by PID Ref Select (A132).

A131 PID Trim Lo

Range:

0.0 to 400.0

Default:

0.0

See also:

N/A

A132 PID Ref Select

Range:

0 = PID Disabled
1 = PID Setpoint
2 = 0-10V Input
3 = 4-20mA Input
4 = Comm Port
5 = Setpnt, Trim
6 = 0-10V, Trim
7 = 4-20mA, Trim
8 = Comm, Trim

Default:

0 = PID Disabled

See also:

P038, A122

A133 PID Feedback Sel

Range:

0 = 0-10V Input
1 = 4-20mA Input
2 = Comm Port

Default:

0 = 0-10V Input

See also:

N/A

A134 PID Prop Gain

Range:

0.00 to 99.99

Default:

0.00

See also:

N/A