Rockwell Automation MD65 User Manual Version 2.0 User Manual
Page 41

Installing Control Wiring
6-7
2-Wire SNK Control -
Non-Reversing
Internal Supply (SNK)
2-Wire SRC Control -
Run FWD/Run REV
P036 (Start Source) =
2, 3 or 4
Input must be active for
the drive to run. When
input is opened, the
drive will stop as
specified by P037
(Stop Mode).
If both Run Forward
and Run Reverse
inputs are closed at the
same time, an
undetermined state
could occur.
Internal Supply (SRC)
External Supply (SRC)
2-Wire SNK Control -
Run FWD/Run REV
Internal Supply (SNK)
3-Wire SRC Control -
Non-Reversing
P036 (Start Source) =
1
A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by P037
(Stop Mode).
Internal Supply (SRC)
External Supply (SRC)
Input/Output
Connection Example
01
02
04
Stop-Run
11
01
02
03
Stop-Run
Forward
Stop-Run
Reverse
Common
01
02
03
04
Stop-Run
Forward
Stop-Run
Reverse
+24V
Each digital input draws 6 mA.
Stop-Run
Forward
Stop-Run
Reverse
01
02
03
04
11
01
02
Stop
Start
01
02
04
+24V
Common
Stop
Start
Each digital input draws 6 mA.