Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 82

Advertising
background image

9-28

MD65 AC Drive User Manual

Enables/disables feature that allows the drive to reconnect to a
spinning motor at actual RPM.

Enables/disables correction options that may improve problems with
motor instability.

1 = Electrical: Some drive/motor combinations have inherent
instabilities that are exhibited as non-sinusoidal motor currents. This
setting attempts to correct this condition.

2 = Mechanical: Some motor/load combinations have mechanical
resonances that can be excited by the drive current regulator. This
setting slows down the current regulator response and attempts to
correct this condition.

Enables/disables a software instantaneous (within 100 ms) current
trip.

A096

Flying Start En

Range:

0 = Disabled
1 = Enabled

Default:

0 = Disabled

See also:

N/A

!

ATTENTION: When starting with this feature
enabled, the motor may temporarily run up to the
maximum speed setting before settling at the speed
setpoint. Stay clear of rotating machinery. Failure to
observe this precaution could result in bodily injury.

A097 Compensation

Range:

0 = Disabled
1 = Electrical
2 = Mechanical
3 = Both

Default:

1 = Electrical

See also:

N/A

A098 SW Current Trip

Range:

0.0 to (Drive Rated Amps x 2)

Default:

0.0 (Disabled)

See also:

P033

Advertising