Rockwell Automation MD65 User Manual Version 2.0 User Manual

Page 84

Advertising
background image

9-30

MD65 AC Drive User Manual

Sets the serial port rate for the RS485 port.

Important:

Power to the drive must be cycled before any changes
will affect drive operation.

Sets the drive node address for the RS485 port if using a network
connection.

Important:

Power to the drive must be cycled before any changes
will affect drive operation.

Selects the drive’s response to a loss of the communication
connection or excessive communication errors.

0 = Fault (Default): Drive will fault on an F81 Comm Loss and coast
to stop.

1 = Coast Stop: Stops the drive via coast to stop.

2 = Stop: Stops the drive via the setting in Stop Mode (P037).

3 = Continu Last: Drive continues operating at communication
commanded speed saved in RAM.

A103 Comm Data Rate

Range:

0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19.2 K
5 = 38.4 K

Default:

4 = 19.2 K

See also:

d015

A104 Comm Node Addr

Range:

1 to 247

Default:

1

See also:

d015

A105 Comm Loss Action

Range:

0 = Fault
1 = Coast Stop
2 = Stop
3 = Continu Last

Default:

0 = Fault

See also:

d015, P037, A106