9-2

MD65 AC Drive User Manual

9.1

Basic Program Group Parameters

The Basic Program Group contains the most commonly used
parameters to simplify the start-up process.

Set to the motor nameplate rated volts.

Set to the motor nameplate rated frequency.

Set to the maximum allowable motor current. The drive will fault on
an F7 Motor Overload if the value of this parameter is exceeded by
150% for 60 seconds or 200% for 3 sec.

Sets the lowest frequency the drive will output continuously.

Sets the highest frequency the drive will output.

P031 Motor NP Volts

Range:

20 VAC to Drive Rated Volts

Default:

Based on Drive Rating

See also:

d004, A084-A087

P032 Motor NP Hertz

Range:

15 to 400 Hz

Default:

60 Hz

See also:

A084-A087, A090

P033 Motor OL Current

Range:

0.0 to (Drive Rated Amps x 2)

Default:

Based on Drive Rating

See also:

A055, A058, A061, A089, A090, A098, A114, A118

P034 Minimum Freq

Range:

0.0 to 400.0 Hz

Default:

0.0 Hz

See also:

d001, d002, d013, P035, A085-A087, A110, A112

P035

Maximum Freq

Range:

0 to 400 Hz

Default:

60 Hz

See also:

d001, d002, d013, P034, A065, A078, A085-A087,
A111, A113