Diagnostics

321

To correct this problem:
• Increase the Link Time Out setup parameter.

• Check the communications setup parameters on the host system and the control.

Host Not Responding
This message displays if communication to the Host system is lost after initial
communication has been established.

To correct this problem:
• Re-establish communications to the host by exiting and re-entering the Upload or

Download to Host screens.

• Review the communications setup parameters on the Host system and the control.

Scale Factor must be between .001 and 1000
This message displays if a value less than .001 or greater than 1000 is entered for a
Scaling Factor.

To correct this problem, enter a value between .001 and 1000 for the Scaling Factor.

Radius at Arc Beginning and Radius at Arc End are not within the Arc
Radial Error Tolerance
This message displays if the radius beginning-arc and the radius-ending arc of a part
program are not within the Arc Radial Error setup parameter in the

Main Setup screen.


To correct this problem:
• Increase the

Arc Radial Error Tolerance setup parameter.

• Correct the part program itself.

Transverse Position Error Exceeded
This message displays if the current Transverse position error exceeds the Servo Error
Tolerance Setup parameter in the machine setups screen. This message also displays if
the position feedback loops are not operating properly, or the machine is being
commanded to move or accelerate faster than it is able.

Generally, this error is displayed if the setting for Incremental or Absolute EIA I and J
codes is set to the wrong state for the active part program. To correct this problem:

• Increase the Servo Error Tolerance Setup parameter in the machine setups screen.
• Re-tune the system.

• Decrease the Maximum machine speed setup or acceleration rate setup parameters.