Configure the Drive

You can include the drive in your Logix Designer application by adding it to a
configured EtherNet/IP module or controller and adding it under the
I/O configuration tree. After setting network parameters, you can view the drive
status information in Studio 5000 software and use it in your Logix Designer
application.

Set the Network Parameters

You must program network parameters by using the LCD display.

1. From the LCD display, select SETUP>NETWORK and choose between

STATIC IP and DHCP.

The default setting is STATIC IP.

2. If STATIC IP, then press to configure the following parameters:

IP address
Gateway
Subnet mask

Settings are stored in nonvolatile memory. IP addressing can also be changed
through the Module Configuration dialog box in RSLinx® software. Changes to
the IP addressing take effect after power is cycled. The drive is factory
programmed to static IP address of 192.168.1.1.

Refer to

Setup Screens

on

page 102

for help setting the network parameters.